Trutest 801: Trutest Sensitivity Testing Head
Trutest 801: Trutest Sensitivity Testing Head

Trutest 801: Trutest Sensitivity Testing Head

Your Price:CAD $11,212.34
Part Number:Trutest 801
  • For individuals who already own Solo 100 telescopic pole.
  • UL Listed Reduces false alarms - a huge problem in the industry.
  • - Battery operated and easily portable
  • - Simple to use
  • - Suits most detectors - both ionization and photoelectric
  • - Calibrated and results in % / ft
  • - Automatically self-calibrates before each test
  • - Measures actual detector sensitivity
  • - Test detectors in place. No need to remove detector
  • - Telescopic adjustment to over 20ft/6m
  • - Battery charge for a complete day's testing
  • - Includes Head Unit Only
  • - Solo Access Pole (Solo 100, Solo 101 or Solo 208) required
Trutest 801 Specifications:
  • Specified at 68øF +/- 5øF < 60% RH using slow ramp
  • All detector types and profiles: (ñ10% of reading + 0.6 %/ft)
  • Size of detectors: All diameters from 2.8in/71mm to 5.7in/145mm
  • Maximum working height: 20ft 8in (6.3m)
  • Average test time: 120 seconds (1%/ft/minute fast ramp, 0.5%/ft/minute slow ramp)
  • Average calibration time:* 40 seconds
  • Average clearing time:* 120 seconds
  • Average tests per aerosol canister: 100 tests
  • Maximum obscuration for ionization: 4.00 %/ft
  • Maximum obscuration for photoelectric: 6.00 %/ft
  • Resolution: 0.01%/ft
  • Average battery life: 8-10 hours testing on a full charge
  • Type of aerosol: Environmentally friendly, non-flammable, non toxic. Safety data sheet available upon request
  • Calibration in operation: Self-calibrates before each testServicing intervals: 1 year recommended, but max interval 5000 tests
  • Operating temperature: 50øF to 95øF (+10øC to 35øC)
  • Storage temperature: 15øF to 120øF (-10øC to 50øC) (Do not store in direct sunlight) ? Humidity: 0-85% RH non-condensing
  • Weight of main unit: 6lb 9oz (3kg) (incl. aerosol canister)
*can be conducted whilst walking between detectors 

Code Requirement: 
CAN/ULC 536-04, 5.7.4.1.3: "Each smoke detector shall be tested to confirm that it is within its rated operating range using a test method described in Clause 5.7.4.1.6.